1

Könnyű


2

Könnyű

What is the base unit of mass in the International System of Units (SI)?


t
N
lb (pound)
kg

3

Közepes

What process takes place in the condenser of a refrigeration system?


The refrigerant rejects only the heat generated in the compressor
The secondary fluid (glycol, water) condenses while the refrigerant evaporates
The refrigerant absorbs heat from the surroundings and evaporates
Hot vapour discharged by the compressor is desuperheated, condensed, and the resulting liquid is slightly subcooled

4

Közepes

What mainly determines the condensing temperature of an air-cooled condenser?


The ambient (inlet) air temperature
The evaporating temperature
The superheat
The compressor discharge temperature

5

Közepes

Why does heat flow from the condenser to the surroundings?


Because the pressure in the condenser is lower than ambient
Because HFC refrigerants attract heat from the surroundings
Because the condensing temperature is higher than the ambient temperature, and heat flows spontaneously from a warmer to a colder body (second law of thermodynamics)
Because the compressor pushes heat directly into the surroundings

6

Közepes

What should you mainly pay attention to when operating a condenser?


Its general condition and the cleanliness of the heat-exchange surfaces
That the outlet air temperature is higher than the condensing temperature
That the inlet air temperature is lower than the outlet air temperature
The colour of the condenser casing

7

Közepes

What criteria should be considered when selecting a suitable condenser?


The required capacity of the condenser and the technical specifications declared by the manufacturer
Only own experience and the dimensions
Only the size and number of fans
Fan noise, connection diameters and colour

8

Közepes

How do contaminants (dust, particulates, deposits) affect the performance and efficiency of heat exchange surfaces in condensers?


Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause an increase in condensing temperature and pressure, which in turn leads to a reduction in the condenser’s efficiency.
Contaminants increase the heat transfer area and reduce the condensing pressure.
Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause a reduction in condensing pressure.
Contaminants do not significantly affect the efficiency and effectiveness of the heat exchange surfaces in condensers.

9

Közepes

How does the capacity of an air-cooled condenser change when it becomes dirty?


It increases because the fan speed rises
It decreases
It remains unchanged
It increases

10

Közepes

What is the main consequence of heavy frost on an air-cooling evaporator?


An increase in condenser subcooling
A rise in evaporating pressure
A rise in the cooled-air temperature with no effect on capacity
Reduced heat transfer and airflow, resulting in a drop in cooling capacity and evaporating temperature

11

Közepes

What happens when the evaporation temperature drops?


The condenser fan speed increases.
The compressor’s cooling capacity increases.
The compressor’s cooling capacity decreases.
The discharge temperature decreases.

12

Közepes

When is natural (off-cycle, air) defrosting possible?


Never – electric heaters must be used in every air cooler
When the air passing through the cooler is above 0 °C
Only in coolers fitted with speed-controlled fans
Only in freezer rooms below −18 °C

13

Közepes

When does frost form on the surface of an air-cooling evaporator?


Only when the system runs continuously
When the evaporator surface temperature is below 0 °C and below the dew point of the air
Only when the room air temperature falls below 0 °C
Always, in every air cooler

14

Közepes

In extensive pipework systems, flash gas (secondary evaporation) in the liquid line can be prevented by…


…increasing the length of the liquid line
…insulating the discharge line between the compressor and the condenser
…using smaller-diameter pipes
…additional subcooling of the liquid

15

Közepes

How does hot gas defrosting of the evaporator work?


We swap the outlet and inlet sides of the evaporator.
We switch on the gas heater directed at the evaporator.
This involves reversing the direction of rotation of the compressor.
Heated vapour (hot gas) from the compressor is directed into the evaporator piping.

16

Közepes

What is the function of the evaporator in a refrigeration system?


It ensures that the refrigerant is superheated over the largest possible heat exchange surface area.
It cools the refrigerant.
It evaporates the water flowing through the evaporator.
It transfers heat from the medium being cooled to the boiling refrigerant.

17

Közepes

What condition must electric heaters for evaporator defrosting meet?


They must be in direct contact with the refrigerant
They must be located beneath the evaporator
They must have good thermal contact with the heat-exchange surface (e.g. inserted in the fin block)
Heat from the heaters must be carried by the running fans

18

Közepes

Refrigerant distributor:


ensures even distribution of the refrigerant to the individual sections of the condenser.
ensures an even distribution of the refrigerant to the individual sections of the evaporator.
acts as a buffer for the refrigerant in the event that the pressure upstream of the expansion valve is exceeded.
ensures the even distribution of the refrigerant discharged by compressors connected in parallel.

19

Közepes

What defrosting methods are used for air coolers?


Natural only – other methods are ineffective and uneconomic
Electric, hot gas, water spray and natural (at positive temperatures)
Only by switching off the fans with the compressor running
Electric only – other methods are not permitted in refrigeration

20

Közepes

The boiling point of a liquid rises when the pressure above the liquid…


…remains constant
…varies depending on the ambient temperature
…rises
…falls

21

Közepes

MOP in thermostatic expansion valves stands for:


self-cleaning of the valve in the event of moisture in the refrigerant freezing.
minimum flow opening.
maximum operating pressure.
maximum pressure switch protection.

22

Közepes

The function of a thermostatic expansion valve (TEV) is:


to meter refrigerant into the evaporator according to the superheat of the vapour leaving the evaporator
to adjust the evaporating pressure in the condenser
to maintain a constant condensing pressure
to maintain a constant compressor suction pressure

23

Közepes

What type of compressor motor can be used with a capillary tube?


A low-speed motor
A high-starting-torque motor must be used
An electronically commutated motor
A low-starting-torque motor (pressures equalise during standstill)

24

Közepes

What does a thermostatic expansion valve control?


The temperature in the cold room
The condensing pressure
The discharge temperature
The mass flow of refrigerant fed into the evaporator

25

Könnyű

The refrigerant absorbs heat when…


…it freezes
…it condenses
…it evaporates
…it is subcooled

26

Közepes

What does the manufacturer state as the factory setting of a thermostatic expansion valve?


the superheat value during valve operation.
the static superheat of the valve.
the degree to which the valve is filled with refrigerant liquid.
the degree of refrigerant expansion.

27

Közepes

Where is a new or repaired system with an expansion valve and liquid receiver charged?


In the liquid phase on the high-pressure side, with the compressor stopped
Through the capillary tube outlet during normal system operation
In the liquid phase into the compressor suction, with the compressor running
Anywhere – the charging point does not matter

28

Közepes

What does a thermostatic or electronic expansion valve control?


Subcooling, by adjusting condensing pressure
The compressor speed
The amount of refrigerant fed to the evaporator according to superheat
The evaporating pressure – closing below the set point

29

Közepes

What does the MOP function of thermostatic expansion valves mean?


The valve maintains a constant condensing pressure
The valve limits the maximum evaporating (suction) pressure, protecting the compressor motor from overload, e.g. after defrost
The valve prevents motor overheating by injecting liquid into the compressor
The valve limits subcooling

30

Közepes

The lower the liquid temperature upstream of the expansion valve, (at the same mass flow)…


…the higher the specific refrigerating effect qo [kJ/kg] and the higher the cooling capacity Qo
…the lower qo and the lower Qo
…the lower qo and the lower energy efficiency
…the lower qo, with Qo unchanged

31

Közepes

How should the MOP point of an expansion valve be selected relative to the highest normal evaporating temperature?


About 7 K lower than that temperature
Higher by approx. 20 K
A few kelvin higher (approximately 7 K)
Freely – the MOP value is irrelevant

32

Közepes

What is the function of the suction pressure regulator?


To maintain the suction pressure at the highest possible level.
It limits the suction pressure and protects the compressor from excessively high suction pressure.
It prevents a drop in suction pressure and, if necessary, shuts down the refrigeration system.
It maintains the evaporation pressure at a constant level.

33

Közepes

What is the function of the valve regulating water flow through the condenser?


To maintain the condensing pressure at the highest possible level.
To maintain the condensing pressure at the lowest possible level.
To maintain the condensing pressure at a constant level.
To maintain the water temperature at the highest level.

34

Közepes

The use of a refrigerant distributor requires a thermostatic expansion valve ...


... with a MOP function.
... with external pressure equalisation.
... with an adsorption-type sensor filling.
... with internal pressure equalisation.

35

Közepes

What properties should good insulation materials have?


The ability to absorb large amounts of moisture
Low thermal conductivity (and low water absorption, vapour tightness)
High thermal conductivity
An antistatic coating

36

Közepes

When is refrigerant vapour superheated?


When its temperature is higher than the saturation temperature corresponding to its pressure
When the evaporating temperature is lower than the ambient temperature
When the compressor motor temperature rises excessively
When the pressure on the discharge side is higher than on the suction side

37

Közepes

How can you check whether the liquid refrigerant is reaching the expansion valve without vapour bubbles?


We check this using a sight glass.
We are unable to check this.
We check using a pressure gauge fitted on the discharge side of the compressor.
We check using a liquid pressure gauge.

38

Közepes

Where does the liquid line run?


Between the compressor and the condenser
Between the evaporator and the compressor
From the condenser (liquid receiver) to the expansion valve
Between the evaporator and the suction-line heat exchanger

39

Közepes

What is the function of the liquid receiver in a refrigeration system?


To further subcool the condensed refrigerant
To collect liquid refrigerant and excess oil
To act as a reserve when the required charge is unknown
To store refrigerant and compensate for changes in the circulating charge as the heat load varies

40

Közepes

What is the purpose of the liquid receiver during service work?


It collects excess oil circulating in the system
It is a reserve when the installer does not know the required charge
It allows pump-down and temporary storage of the refrigerant
It further subcools the refrigerant before the expansion valve

41

Közepes

Where should the liquid receiver be installed?


It should be fitted just before the compressor.
It should be installed downstream of the condenser, upstream of the expansion valve.
It should be fitted between the compressor and the condenser.
It should be fitted after the evaporator.

42

Közepes

What is the function of the suction pressure regulator fitted to the suction pipe when the compressor starts up?


It regulates the condensing pressure.
It regulates the evaporation pressure.
It opens when the suction pressure upstream of the compressor drops.
It closes when the suction pressure upstream of the compressor drops.

43

Közepes

The use of microchannel heat exchangers, compared with conventional heat exchangers made of copper tubes and fins, results in:


There is no effect whatsoever on either the amount of refrigerant or energy efficiency.
A reduction in refrigerant charge and, typically, higher energy efficiency.
An increase in the amount of refrigerant in the system and an increase in condensing pressure.
A reduction in the system’s energy efficiency.

44

Közepes

Which refrigerants belong to the HFC group?


R134a, R32, R22, R507A, R290.
R134a, R404A, R507A, R410A.
R11, R12, R502.
R22, R401A.

45

Közepes

Which refrigerants belong to the HFO group?


R22, R12.
R134a, R404A.
R1234yf, R1234ze(E).
R134a, R290.

46

Közepes

What are the characteristics of R410A refrigerant compared to R407C refrigerant?


The saturation pressure of R407C refrigerant is much higher than that of R410A.
The saturation pressure of R407C is 150% higher than that of R410A.
The saturation pressure of R410A refrigerant is higher than that of R407C.
The saturation pressure of both refrigerants is roughly the same.

47

Közepes

What does the TEWI indicator define?


Total Equivalent Warming Impact: the sum of direct emissions (leakage and refrigerant losses at disposal) and indirect emissions (CO₂ from generating the energy consumed by the equipment) over its lifetime
The ability of the ozone layer to recover
The global warming potential of a gas relative to CO₂ over a 100-year horizon
The impact of a refrigerant on the ozone layer

48

Közepes

What are the characteristics of R452A compared with R404A?


Both are azeotropic and have no temperature glide
The temperature glide of R452A is half that of R404A
It is a flammable and toxic single-component HFC
It is a non-flammable (A1) HFC/HFO blend with properties similar to R404A and a GWP about 45% lower

49

Közepes

What distinguishes R1234yf from R134a?


A higher critical temperature
Higher toxicity
It is mildly flammable (class A2L), whereas R134a is non-flammable (A1)
A higher normal boiling point

50

Közepes

How does CO₂ (R744) compare with R134a?


It has identical properties and is a drop-in replacement for R134a
Unlike R134a, it is an azeotropic mixture
It has a lower critical temperature, much higher operating pressures and a much higher volumetric cooling capacity (smaller compressors and pipes)
Its temperature glide is 7 K greater than that of R134a

51

Közepes

Which of the following is NOT a fluorinated greenhouse gas?


Perfluorocarbons (PFCs).
Carbon dioxide (CO₂).
Hydrofluorocarbons (HFCs).
Sulphur hexafluoride (SF6).

52

Nehéz

What additional protective equipment will you use when brazing systems containing HC refrigerants?


Ear defenders
A high-visibility vest
A flammable gas detector
Latex gloves

53

Nehéz

Why can’t a sealed high-pressure switch be replaced with a standard mechanical one in a system containing a flammable refrigerant?


It is a potential source of ignition
The pressure switch setting will not be correct
There is a risk of refrigerant leakage
Dust and moisture may enter

54

Nehéz

What is the minimum (recommended) distance from a work area with HC refrigerants within which there must be no sources of ignition?


2 m
3 m
0.5 m
1 m

55

Nehéz

What is the maximum safe R32 fill of a recovery cylinder approved for flammable gas that holds 20 kg of R410A (the liquid density of R32 is about 8-10% lower)?


18 kg
33 kg
9 kg
20 kg

56

Nehéz

What is the maximum charge of an A3 refrigerant for a hermetic display cabinet with an integral condenser located in the ground-floor sales area of a supermarket?


10 kg
1.0 kg
0,494 kg
2.5 kg

57

Nehéz

How can a vacuum pump be used safely to evacuate a system containing a flammable refrigerant?


Place the pump directly on the floor, as low as possible
Position the pump at least 3 m above floor level
Ignition-source-free pump, good ventilation, exhaust to a safe place
Such systems need not be evacuated before charging

58

Közepes

What is the greenhouse effect?


Dust in the atmosphere reflects sunlight, lowering the average surface temperature
Clouds reflect ultraviolet radiation, which makes the air near the surface warmer
Greenhouse gases absorb and re-emit the Earth's infrared radiation, warming the lower atmosphere
Chlorine compounds destroy stratospheric ozone, increasing UV radiation at the surface

59

Nehéz

What safety measure must you carry in your vehicle when transporting flammable refrigerant cylinders?


A fire extinguisher
Thick gloves
A fire blanket
Tinted safety goggles

60

Nehéz

How would you prepare a 10 kg R32 water chiller located outdoors for debrazing its joints?


Vent the R32 outdoors, then fill and vent the system with nitrogen three times
Vent the R32 outdoors and purge the system
Recover the R32 to a vacuum and start desoldering immediately
Recover the R32 to a vacuum, then fill the system with nitrogen to a slight positive pressure (approx. 0.1 bar g)

61

Közepes

What is R1270?


Propane
Isobutane
n-Butane
Propene (propylene)

62

Nehéz

Which of the following leak detection methods should NOT be used to locate an HC refrigerant leak?


Leak detection foam
Electronic leak detector for flammable refrigerants
Electronic HFC leak detector
Soapy water solution

63

Nehéz

What is the most important difference between a flammable refrigerant recovery unit and a standard one?


A different colour for the station
Different connection sizes
Different low-pressure switch setting
A flammable refrigerant recovery unit has no ignition sources

64

Nehéz

Which of the following is a source of ignition?


An 'n'-type (non-sparking) thermostat
A contactor (sparking contacts)
An Ex-certified fan motor
A sealed NTC temperature sensor

65

Nehéz

What particularly hazardous substance is formed when R32 burns?


Hydrogen fluoride (HF)
Phosgene
Sulphur dioxide (SO₂)
Hydrogen chloride (HCl)

66

Nehéz

What type of refrigerant is R1234ze(E)?


CFC (chlorofluorocarbon)
HCFC (hydrochlorofluorocarbon)
HC (hydrocarbon)
HFO (hydrofluoroolefin)

67

Nehéz

What hazards does a safety group A3 refrigerant pose?


Higher toxicity, higher flammability
Lower toxicity, moderate flammability
Lower toxicity, higher flammability
Higher toxicity, moderate flammability

68

Nehéz

According to EN 378, what is the maximum R290 charge in a cold room measuring 5 m × 3 m × 2.5 m (LFL of R290 = 0.038 kg/m³, access category a, location class I, no additional measures))?


4.93 kg
0.285 kg
1.5 kg
1.0 kg

69

Könnyű

What does the GWP indicator mean?


The annual rise in mean air temperature caused by the emission of 1 kg of the gas
The ability of a substance to restore the ozone layer
Ozone depletion potential
Global Warming Potential: the climate warming impact of 1 kg of a gas compared with 1 kg of CO₂ (GWP = 1) over a defined time horizon, usually 100 years

70

Nehéz

What is the approximate ratio of the volumetric cooling capacity of R32 to that of R410A (same compressor and conditions)?


approx. 1.3
approx. 1.05–1.1
approx. 0.75
approx. 0.6

71

Nehéz

Why are Ex-certified evaporator fan motors used in some systems with flammable refrigerants?


Because they must be kept running continuously to disperse the leaking refrigerant
Because they are more energy-efficient
To avoid a source of ignition in the event of a flammable refrigerant leak
Because they are more reliable

72

Nehéz

Why is the density difference between HC and HFC refrigerants important?


Because HCs must be charged much more slowly than HFCs
Because HCs operate at much higher pressures
Because it determines the system's energy efficiency
An HC charge in kg is roughly half that of an HFC

73

Nehéz

What is the GWP of R290 according to Annex VI to Regulation (EU) 2024/573?


0.02
150
7
675

74

Nehéz

Which of the following is NOT a source of ignition?


An Ex-certified fan motor
A light switch
An electrical switch
An unsealed mechanical pressure switch

75

Nehéz

What is R290?


Butane
Propane
Isobutane
Propene (Propylene)

76

Nehéz

What is the maximum A2L charge for a hermetic display cabinet with integral condenser in the ground-floor sales area of a supermarket?


1.5 kg
2.5 kg
150 g
1.2 kg

77

Nehéz

Why can’t a standard relay be fitted when retrofitting a compressor’s electrical system for flammable refrigerants?


It could be a source of ignition
A relay is never required for compressors using flammable refrigerants
Current consumption differs for compressors using flammable refrigerants compared to those using HFCs
The method of starting the compressor motor differs from that used with HFCs

78

Nehéz

What is the minimum (recommended) distance from a work area with HC refrigerants within which there must be no ignition sources?


1 m
10 m
5 m
3 m

79

Nehéz

A recovery cylinder holds 10 kg of R404A (filling ratio 0.82 kg/l). What is the maximum R290 charge for this cylinder (propane filling ratio 0.43 kg/l per ADR P200)?


approx. 5.2 kg
approx. 17 kg
20 kg
approx. 8 kg

80

Közepes

How do refrigeration systems contribute to the greenhouse effect?


Only through the heat rejected by the condenser
Indirectly (through energy consumption) and directly (through emissions of refrigerant into the atmosphere)
Only through CO₂ given off by the compressor motor
Through oil emitted into the atmosphere from the condenser and filter

81

Nehéz

How can a vacuum pump be used safely to evacuate a system containing R290?


Position the pump at least 3 m above floor level
R290 systems need not be evacuated before charging
Ignition-source-free pump, good ventilation, exhaust to a safe place
Place the pump directly on the floor, as low as possible

82

Nehéz

Under ADR, what equipment must you carry in your vehicle when transporting flammable refrigerant cylinders (under the 1.1.3.6 exemption)?


A fire extinguisher (at least 2 kg dry powder)
Thick gloves
Tinted safety goggles
A fire blanket

83

Nehéz

How do you make sure it is safe to light the torch for desoldering joints in a system from which a flammable refrigerant has been removed?


Ensure good ventilation and check the work area with a flammable gas detector
Such joints must never be desoldered; they must be cut with a pipe cutter
Working outdoors is sufficient
Purge the system with compressed air

84

Nehéz

How would you prepare a system containing 100 g of R1270 for debrazing, if local regulations allow controlled venting of small HC quantities?


Recover the R1270 to a vacuum and start brazing immediately without a nitrogen purge
Vent the R1270 into the room and open a window
Vent the R1270 to a safe outdoor location, then purge with OFN three times (pressurise and vent), and braze with OFN flowing
Vent the R1270 outdoors and start brazing immediately

85

Nehéz

Which method should NOT be used to locate an R290 leak?


Leak detection foam
Fluorescent dye and UV lamp (if approved by the manufacturer)
An electronic detector for flammable refrigerants
An electronic leak detector designed for HFCs

86

Nehéz

Why can’t recovery stations designed for HFCs be used with R600a?


The oil in the recovery unit is not soluble in R600a
The recovery unit cannot withstand the working pressure of R600a
The low-pressure switch setting will not be suitable for R600a due to its lower operating pressure
They contain ignition sources

87

Nehéz

According to EN 378, what is the maximum R1234ze(E) charge in a cold room measuring 5 m × 3 m × 2.5 m (LFL = 0.303 kg/m³, access category a, location class I, no additional measures)?


2.27 kg
227 kg
618 kg
6.18 kg

88

Nehéz

What type of refrigerant is R32?


Hydrofluorocarbon
Carbon dioxide
Hydrocarbon
Hydrofluoroolefin

89

Nehéz

What hazards do A2L refrigerants pose?


Higher toxicity, lower flammability
Lower toxicity, higher flammability
Lower toxicity, lower flammability (burning velocity ≤ 10 cm/s)
Higher toxicity, higher flammability

90

Nehéz

What hazard is associated with the combustion of HFO or HFC refrigerants?


Ozone is formed
Phosgene is formed
Nitrous oxide is formed
Hydrogen fluoride (HF) is formed

91

Közepes

What is the greenhouse effect?


The formation of a layer that traps only heat from fuel combustion in aircraft
The trapping of heat in the Earth's atmosphere, which hinders the radiation of heat into space
The absorption of solar radiation by the Earth's surface
The filtering of solar radiation by the atmosphere

92

Nehéz

Approximately what compressor displacement is required for R600a compared with R134a for the same cooling capacity?


About twice as large
About seven times as large
About half
The same

93

Nehéz

What is the GWP value for R32 according to Regulation (EU) 2024/573?


3
7
675
0

94

Nehéz

Why is charge accuracy more important in critically charged R290 systems than in HFC systems?


The charge mass is much smaller than in an HFC system, because the liquid density of R290 is much lower
Because of lower operating pressures
Because R290 is only used in systems below 150 g
Because such systems never have liquid receivers

95

Nehéz

Why does the condenser fan run continuously in some systems using R1270?


To reduce energy consumption
To prevent the build-up of contaminants in the condenser
To dilute the refrigerant in the event of a leak
To ensure that the discharge pressure never becomes excessive

96

Közepes

Which EU regulation is currently the primary piece of legislation governing the use of fluorinated greenhouse gases (F-gases) in the European Union?


Regulation (EU) 2024/573
Regulation (EU) No 517/2014
Directive 2009/125/EC
Regulation (EU) 2015/1188

97

Közepes

What is the main objective of Regulation (EU) 2024/573?


To facilitate the import of electrical appliances
To reduce taxes on refrigeration equipment
Standardising metal recycling standards
Prevention of F-gas emissions and the achievement of the EU’s climate targets

98

Közepes

What are the ecodesign obligations of manufacturers of refrigerating appliances?


Only declaring F-gas quantities under Regulation (EU) No 517/2014
Only using energy labels under Regulation (EU) 2024/573
Meeting implementing regulations (e.g. 2019/2019, 2015/1095): efficiency, spare parts, reparability
Only implementing an ISO 9001 quality management system

99

Közepes

What is the main objective of EU ecodesign legislation (Directive 2009/125/EC, now Regulation (EU) 2024/1781 – ESPR)?


To facilitate imports from outside the EU
To standardise the appearance of products in the EU
To reduce the negative environmental impact of products by improving energy efficiency, durability and recyclability
To increase sales of electrical appliances in the EU

100

Közepes

What is the function of a ball valve in a refrigeration system?


It regulates the temperature of the refrigerant
It prevents excessive pressure build-up in the system
Enables the refrigerant flow to be completely shut off
It measures the moisture content of the refrigerant

101

Könnyű

What is the main function of a safety valve?


It controls the oil level in the compressor
Prevents the evaporator from freezing
It monitors the moisture content of the refrigerant
Discharges refrigerant when the set pressure is exceeded

102

Közepes

How do certain gases contribute to the greenhouse effect?


They heat the air through chemical reactions with atmospheric oxygen and nitrogen
They limit UV radiation reaching the Earth's surface, changing the heat balance
They deplete the ozone layer, so more solar radiation reaches the surface
They trap thermal radiation that the Earth would otherwise emit into space

103

Közepes

What is the purpose of a sight glass (with moisture indicator)?


Regulating compressor pressure
Measuring condenser temperature
Visual assessment of the refrigerant condition in the liquid line (bubbles) and of system moisture
Emergency shut-off of flow

104

Közepes

What is the function of the temperature regulator in a refrigeration system?


It drains excess refrigerant into the receiver
To maintain a constant pressure in the compressor
Controls the operation of the compressor and valves to maintain the set temperature
It restricts oil flow

105

Nehéz

What is the role of a suction liquid separator (also in systems with flammable or toxic refrigerants)?


It heats the refrigerant before the evaporator
It separates liquid from oil
It prevents liquid refrigerant from entering the compressor
It is used only to measure moisture

106

Nehéz

What is the function of an oil separator in systems using flammable or toxic refrigerants?


Heats the refrigerant before it enters the evaporator
Separates oil from the refrigerant and facilitates the return of oil to the compressor
They are used solely to measure the moisture content of the refrigerant
It prevents liquid from entering the compressor

107

Közepes

What is the purpose of oil level regulators in a refrigeration system?


They control the evaporator temperature
They control the pressure in the condenser
Maintains the correct oil level in the compressor
They drain off excess refrigerant

108

Közepes

What is the function of the liquid receiver in relation to system tightness?


It regulates the oil returning to the compressor
It stores refrigerant; checking its liquid level helps detect charge loss
It keeps the whole system at constant pressure regardless of load
It controls the evaporating temperature by varying the circulating charge

109

Közepes

What is the role of a gauge manifold with thermometers (temperature probes)?


It monitors refrigerant moisture content
It measures pressures and temperatures to determine superheat and subcooling and thus assess the system charge (indirect leak check)
It relieves pressure if it is exceeded
It controls oil level

110

Közepes

What is the role of defrost controls?


They drain excess oil from the evaporator to the receiver
They control compressor discharge pressure during defrost
They monitor the moisture content of the refrigerant
They protect the evaporator from icing and damage that could lead to leaks

111

Nehéz

Why do liquid and oil separators in CO₂ systems require particular attention?


Because CO₂ needs no lubrication, so oil separators are unnecessary
Because CO₂ is flammable and separators must not be used
Because of very high pressures – adequate PS and protection devices are required
Because sight glasses and level indicators must not be used in CO₂ systems

112

Nehéz

What is the critical pressure of CO₂ (R744)?


Approx. 120 bar
Approx. 74 bar (abs)
Approx. 31 bar
Approx. 10 bar

113

Könnyű

What is the unit of pressure in the International System of Units (SI)?


Pa (pascal)
bar (gauge)
psi (pound per square inch)
atm (standard atmosphere)

114

Közepes

Where can the lists of fluorinated greenhouse gases be found?


In Annexes I–III to Regulation (EU) 2024/573 of the European Parliament and of the Council
In the national Act on ozone-depleting substances and certain fluorinated greenhouse gases
In the Vienna Convention for the Protection of the Ozone Layer
In a regulation of the Minister of Economy on the list of fluorinated greenhouse gases

115

Nehéz

What characterises the transcritical process in CO₂ systems?


Conventional condensation occurs
Heat rejection takes place above the critical point – the refrigerant does not condense in the conventional way (gas cooler instead of condenser)
It is irrelevant to system operation
It occurs only at low temperatures

116

Nehéz

What characterises the subcritical CO₂ process?


The absence of condensation
The absence of evaporation
Operation above the critical point
The conventional condensation process below the critical point

117

Könnyű

What is the log(p)-h diagram for CO₂ used for?


To detect leaks
For analysing thermodynamic processes in a refrigeration system
To measure temperature
To regulate pressure

118

Könnyű

What can be read from the log(p)-h graph?


Only the temperature
Pressure, enthalpy, temperature and state of the refrigerant
Only the humidity
Only the amount of refrigerant

119

Könnyű

What are CO₂ saturation tables used for?


To determine the oil quantity
To regulate the compressor
To measure humidity
To determine the relationship between temperature and pressure at saturation

120

Könnyű

What does the CO₂ saturation state mean?


Equilibrium between the liquid and vapour phases
A state in which the refrigerant is only a gas
A state of high pressure
Dry ice state

121

Nehéz

When can dry ice (solid CO₂) form?


During normal operation of the system
When the pressure drops suddenly below the triple point (approx. 5.2 bar abs, −56.6 °C), e.g. when venting liquid CO₂ or charging liquid into an evacuated system
At high pressure
At high temperature

122

Nehéz

What risks are associated with dry ice forming in a CO₂ system?


Blocked pipes and valves and system damage (and a sharp pressure rise when it thaws)
Improved efficiency
Pressure reduction
No risk

123

Nehéz

How does CO₂ saturation pressure change as temperature increases?


It increases rapidly
It first decreases, then increases
It decreases
It remains the same

124

Könnyű

Why is understanding the log(p)-h graph particularly important for CO₂?


It doesn’t matter
As CO₂ systems operate in different modes (sub- and transcritical) and require detailed analysis
It only applies to NH₃
It is only used for design purposes

125

Közepes

Where can the lists of ozone-depleting substances be found?


In the Vienna Convention for the Protection of the Ozone Layer
In a regulation of the Minister of the Environment on the list of controlled substances
In Annexes I and II to Regulation (EU) 2024/590 of the European Parliament and of the Council
In the national Act on ozone-depleting substances and certain fluorinated greenhouse gases

126

Nehéz

What happens to CO₂ above the critical point?


It transitions to a supercritical state (no distinction between liquid and gas)
It ceases to conduct heat
It turns into a liquid
It turns into a solid

127

Könnyű

Why do CO₂ systems require precise pressure control?


Due to significant pressure changes with temperature fluctuations
Because there are no valves
Due to low pressures
They do not require control

128

Közepes

Why is ammonia (R717) classed as a toxic refrigerant?


Because it is heavier than air and displaces oxygen
It severely irritates the respiratory tract, eyes and skin, and is poisonous when inhaled at higher concentrations
Because it is colourless and odourless and therefore hard to detect
Because it does not react with water, making neutralisation difficult

129

Nehéz

What is the main difference between a dry-expansion and a flooded evaporator?


In a dry-expansion evaporator the refrigerant completely evaporates and is superheated in the evaporator; in a flooded one part of the refrigerant remains liquid (incomplete evaporation, no superheat)
A dry-expansion evaporator needs no expansion valve, a flooded one does
A dry-expansion evaporator always has a lower pressure than a flooded one
A dry-expansion evaporator is filled with liquid, a flooded one with vapour

130

Nehéz

What is the typical pressure in the evaporator of an R717 deep-freeze system (below −40 °C)?


Positive pressure of 5–10 bar
Positive pressure of 10–20 bar
Below atmospheric (approx. 0.7 bar abs at −40 °C)
Atmospheric pressure, approx. 1 bar abs

131

Nehéz

Why are PFAS formed by the decomposition of certain F-gases (e.g. TFA from HFOs) problematic?


They are climate- and environment-neutral
They are readily biodegradable
They cause rapid cooling of the atmosphere
They are very persistent, accumulate in the environment (e.g. water) and may be toxic

132

Könnyű

What is the basic requirement when charging a system with R717 (NH₃)?


NH₃ can be charged together with air
Charging must only take place at temperatures below 0°C
Charging should take place in a well-ventilated area using appropriate personal protective equipment
Charging can be carried out without personal protective equipment

133

Nehéz

How is oil managed in R717 systems?


Oil has no effect on system operation
Oil can be mixed with any refrigerant
Oil collecting at the lowest points of vessels is regularly checked and drained, because it impairs heat transfer
Oil requires no monitoring

134

Könnyű

What is the correct procedure for recovering R717 from a system?


Recovery is not required
The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃
The refrigerant can be drained into the sewer system
The gas can be released into the atmosphere

135

Könnyű

How should R717 (NH₃) be stored?


In unmarked plastic containers
In sealed, labelled containers, in a cool and well-ventilated place
Near heat sources
In any open containers

136

Közepes

Where and by when must entities obliged under the Polish Act of 15 May 2015 submit annual reports on ODS and F-gases?


By 31 January, in the Central Register of Operators (CRO)
By the end of the calendar year, on a form at a regional office of the Office of Technical Inspection (UDT)
By 28 February of the following year, electronically via the Reports Database (BDS) run at the Institute of Industrial Chemistry (ICHP)
By 31 March, electronically to the Ministry of Climate and Environment

137

Nehéz

What should be done with contaminated R717?


Continue to use it without restriction
Dilute it with water and reuse it
Release it into the atmosphere
Purify it or send it for disposal in accordance with regulations

138

Könnyű

What is the main hazard associated with an R717 leak during maintenance work?


No risk whatsoever
Toxic to humans and may cause chemical burns
Damage to electrical equipment only
Increased cooling efficiency

139

Nehéz

What should be done if an NH₃ leak is detected?


Evacuate people immediately and raise the alarm; stop the leak only if it is safe to do so and with suitable PPE (respiratory protection)
Increase the pressure in the system
Carry on working wearing a dust mask
Carry on working with the room door open

140

Nehéz

What role do scrubbers play in NH₃ systems?


They are used to measure temperature
Neutralise ammonia through absorption in a liquid (e.g. water)
They store the refrigerant
They increase the pressure in the system

141

Nehéz

How should the system be prepared before filling with R717?


There is no need to check it
Check for leaks, remove air and moisture, and create a vacuum
Simply start it up
The pressure must be increased above the standard level

142

Nehéz

What are the transport requirements for R717?


It must be carried in suitable, labelled packagings in accordance with ADR (UN 1005, class 2, code 2TC)
It can be carried in open containers
Transport is not regulated
It can be carried without labelling

143

Könnyű

What personal protective equipment is required when working with NH₃?


No requirements
Workwear only
Only a safety helmet
Safety goggles, gloves and respiratory protective equipment

144

Közepes

Which installation measure has a major impact on compressor energy efficiency?


Proper evacuation and dehydration of the system (removing air and moisture)
Omitting the filter-drier to reduce flow resistance
Charging extra refrigerant 'as a reserve' above the nameplate value
Installing a suction line smaller than recommended

145

Közepes

How does regular oil-level monitoring affect compressor operation?


It allows any type of oil to be topped up
It increases cooling capacity above nominal
It allows the crankcase heater to be omitted
It ensures proper lubrication and limits wear and energy losses

146

Könnyű

How do system leaks affect compressor energy efficiency?


No effect as long as the system still cools
They improve efficiency because condensing pressure drops
They affect only safety, not energy use
Refrigerant loss reduces capacity and increases energy use (longer run times, higher superheat)

147

Közepes

Regulation (EU) 2024/590 relates to:


Conditions for F-gas certification of companies recovering and reclaiming refrigerants
Health and safety during refrigerant recovery
Alternative refrigerants replacing fluorinated greenhouse gases
Ozone-depleting substances

148

Közepes

What is the significance of proper suction and discharge pressure control?


The highest possible condensing pressure is best
Pressures do not affect energy use
The lowest possible suction pressure is best
It keeps the compressor at optimal conditions (suction pressure as high and condensing pressure as low as permissible)

149

Közepes

Which maintenance measure reduces compressor energy consumption?


Replacing the filter-drier when the pressure drop or moisture indicator shows it is necessary
Topping up refrigerant at every service visit
Raising the high-pressure switch setting
Permanently disabling the crankcase heater

150

Közepes

How does air (non-condensable gas) in the system affect operation?


It lowers the condensing pressure
It raises the condensing pressure and reduces efficiency
It only affects the sight-glass indication
It improves condenser heat transfer

151

Közepes

What role do controls play in compressor efficiency?


They matter only in NH₃ systems
They enable optimised operation and lower energy use (e.g. floating head pressure, capacity matching)
They provide safety only, with no energy effect
They increase the circulating refrigerant charge

152

Közepes

How does suction superheat at the compressor affect efficiency?


Excessive superheat reduces efficiency and raises the discharge temperature
Zero suction superheat is optimal
Superheat has no effect
The higher the superheat, the higher the efficiency

153

Közepes

How does correct system layout affect efficiency?


Longer pipes improve subcooling and always increase efficiency
It doesn't matter
It affects only appearance
It shortens pipe runs and limits pressure drops and energy losses

154

Közepes

How important is suction pipe insulation?


It limits heat gain and excessive superheat, improving efficiency
It increases energy consumption
It is needed only for appearance
It has no effect

155

Közepes

Which measure most improves condenser energy efficiency?


Raising the condensing pressure set point
Regular cleaning of heat-exchange surfaces
Reducing fan speed to the minimum
Increasing the refrigerant charge

156

Könnyű

How does a dirty condenser affect the operation of the refrigeration system?


Causes an increase in pressure and energy consumption by the compressor
It improves efficiency
It has no effect
It lowers the condensing pressure

157

Könnyű

Why is adequate airflow through an air-cooled condenser important?


It ensures effective heat rejection and low condensing pressure
It affects only noise
It doesn't matter
The lower the airflow, the lower the condensing pressure

158

Közepes

Which refrigerants damage the ozone layer?


All refrigerants containing fluorine and hydrogen in their molecules
All natural refrigerants
All refrigerants containing chlorine or bromine in their molecules
All refrigerants containing carbon in their molecules

159

Könnyű

How does the presence of limescale in a water-cooled condenser affect performance?


It has no effect
It improves heat transfer
It lowers the condensation temperature
Impairs heat exchange and increases energy consumption

160

Közepes

How does correct condensing pressure control affect efficiency?


It is best to keep a constant high condensing pressure all year
It keeps the lowest pressure that still ensures proper expansion-valve feed, reducing energy use
It always increases energy use
It has no effect

161

Könnyű

How do condenser leaks affect energy efficiency?


Have no effect
They improve efficiency
Causes refrigerant loss and a drop in efficiency
They lower the temperature

162

Könnyű

How important is the correct positioning of an air-cooled condenser?


It should be housed in a small room
It should be installed in a well-ventilated area with unobstructed airflow
It should be close to heat sources
It doesn’t matter

163

Könnyű

How does hot air recirculation affect the condenser?


It improves efficiency
It has no effect
It reduces the pressure
Impairs cooling and increases energy consumption

164

Közepes

How does insulation of heating and DHW pipework affect the efficiency of a heat pump system?


It reduces energy losses and improves overall system efficiency
It increases pressure
It impairs cooling
It doesn't matter

165

Közepes

Which measure most improves the energy efficiency of an air-cooling evaporator?


Raising the condensing temperature by a few kelvin
Increasing the refrigerant charge above nominal
Restricting the airflow through the evaporator
Defrosting at the right time and keeping the fins clean

166

Könnyű

How does evaporator icing affect the system’s operation?


Impairs heat exchange and increases energy consumption
It improves cooling performance
It has no effect
It lowers the condensation temperature

167

Könnyű

How does dirt on the evaporator surface affect its performance?


Impairs heat exchange and increases energy consumption
It has no effect
It reduces the pressure
It improves efficiency

168

Könnyű

What maintenance task is crucial for the evaporator?


Regular cleaning and defrosting
Increasing the refrigerant charge
Reduced airflow
Lack of maintenance

169

Közepes

What does a Certificate A2 for natural persons (Implementing Regulation (EU) 2024/2215) authorise?


All activities involving equipment using CO₂ (R744)
All activities (leak checks, installation, repair, maintenance, servicing, decommissioning, recovery) involving F-gases and hydrocarbons in equipment containing less than 3 kg, or less than 6 kg in labelled hermetically sealed systems
Only leak checks that do not entail breaking into the refrigerant circuit
Only recovery of F-gases from equipment containing less than 3 kg (or 6 kg in hermetically sealed systems)

170

Könnyű

How does superheat at the evaporator outlet affect efficiency?


It has no effect
Excessive superheat reduces energy efficiency
It always improves performance
It only causes a temperature drop

171

Könnyű

How do leaks in the evaporator affect efficiency?


Have no effect
Increase capacity
Improves performance
These cause refrigerant loss and a drop in efficiency

172

Könnyű

How important is correct expansion valve adjustment?


Ensures optimal evaporator charge and improves efficiency
It increases energy consumption
Causes leaks
It doesn’t matter

173

Könnyű

How does inadequate insulation of suction (or secondary-coolant) pipes affect evaporator performance?


It has no effect
It causes cooling losses and increased energy use
It lowers the condensing temperature
It improves efficiency

174

Könnyű

How does correct TEV adjustment affect system energy efficiency?


It has no effect
It ensures optimal superheat and improves efficiency
It increases energy use
It causes leaks

175

Könnyű

What happens if the superheat set by the TEV is too high?


The refrigerant charge will increase
It has no effect
Efficiency will drop because the evaporator is not being fully utilised
Cooling efficiency will improve

176

Közepes

How does too low superheat setting on the TEV affect performance?


It has no effect
It reduces refrigerant flow
It may lead to improved efficiency, but it increases the risk of the compressor becoming flooded with liquid
It increases operational safety

177

Könnyű

How do contaminants in the system affect the operation of the TEV?


Have no effect
They lower the temperature
They improve its performance
They can cause it to become blocked and reduce efficiency

178

Könnyű

What role does the filter-drier play in terms of system efficiency?


Removes moisture and contaminants, improving the system’s efficiency
It doesn’t matter
It lowers the temperature
It increases the amount of refrigerant

179

Könnyű

How does proper insulation of components (e.g. pipes near the TEV) affect the system?


It causes leaks
It increases energy consumption
It doesn’t matter
Prevents unwanted heat gains and improves efficiency

180

Közepes

What is the scope of Regulation (EU) 2024/573?


Design requirements and conformity assessment for pressure equipment
Limiting emissions, use and marketing of F-gases, HFC phase-down, certification and reporting
Only requirements for periodic leak checks of refrigeration equipment
Health and safety requirements for brazing and welding on refrigeration installations

181

Könnyű

How important is it to check the operation of the condensing pressure control valve in the system?


Ensures operation within the optimum pressure range and reduces energy losses
It causes a significant rise in temperature
It has no effect
It increases energy consumption

182

Könnyű

How does the correct selection of a TEV affect energy efficiency?


It increases the amount of refrigerant
Ensures the system is matched to its capacity and operates optimally
It lowers the temperature
It doesn’t matter

183

Közepes

What is the main design difference in hydrocarbon refrigeration systems?


The need to eliminate ignition sources and limit the charge because of the refrigerant's flammability
No need for safety measures
Lower energy efficiency
Higher operating pressures

184

Közepes

How do compressors used in hydrocarbon systems differ?


They must be approved by the manufacturer for the specific flammable refrigerant (e.g. electrical components that are not ignition sources, suitable oil)
They must operate at higher pressures than HFC compressors
They need no lubrication
There is no difference

185

Nehéz

What is the main characteristic of R744 (CO₂) refrigeration systems?


Very high operating pressures
Low operating pressures
Low energy efficiency under all conditions
No need for control

186

Nehéz

What are the requirements for piping materials in CO₂ systems?


It doesn't matter
Any material may be used
They must withstand high pressures (e.g. stainless steel, high-strength copper-alloy tubes such as K65)
Only plastics

187

Nehéz

How does a booster system work in CO₂ installations?


It is used to store refrigerant
It reduces the refrigerant quantity
It reduces evaporator pressure
Low-temperature (LT) compressors discharge into the suction of medium-temperature (MT) compressors – two-stage compression in a single circuit

188

Könnyű

What is the function of high-pressure control valves in CO₂ systems?


They control the pressure on the high-pressure side and optimise system operation
They regulate oil flow
They lower the evaporator temperature
They are used to store the refrigerant

189

Nehéz

Why is pressure optimisation in CO₂ systems crucial?


It reduces the ambient temperature
It reduces the amount of refrigerant
It enables the system to achieve maximum energy efficiency in transcritical mode
It doesn’t matter

190

Nehéz

What role does parallel compression play in CO₂ systems?


It increases energy consumption
It has no significance
It compresses flash gas from the intermediate receiver directly to high pressure, improving efficiency
It lowers the ambient temperature

191

Közepes

How can you tell that the system has been overcharged with refrigerant?


Under normal operating conditions the condensing pressure and subcooling rise markedly because excess liquid floods the condenser and reduces its active surface
It cannot be checked, because the sight glass is not intended for this
The compressor runs at a lower load and the suction pressure drops
Even under a very small heat load, frost forms on the suction line

192

Nehéz

How does an ejector work in a CO₂ system?


It increases the amount of refrigerant
It lowers the evaporator temperature
It uses the energy of the higher-pressure refrigerant to raise the pressure of the refrigerant from the lower stage, which improves efficiency
Stores the refrigerant

193

Nehéz

What is the function of liquid ejectors in CO₂ systems?


They raise the refrigerant temperature
They reduce atmospheric pressure
They return liquid from the separator and allow partially flooded evaporator operation (better evaporator feed)
They increase the amount of oil

194

Nehéz

What are the characteristics of partially flooded systems in CO₂ systems?


The absence of liquid in the evaporator
Lack of regulation
Low operating pressure
The presence of liquid in the evaporator, which improves heat transfer and efficiency

195

Nehéz

What is the main risk associated with standstill pressure in CO₂ systems?


A drop in temperature
Increased efficiency
A pressure rise as the refrigerant warms up during standstill (possibly exceeding PS and lifting the relief valves)
A decrease in refrigerant quantity

196

Nehéz

How is standstill pressure limited in CO₂ systems?


By increasing the refrigerant charge
By using an auxiliary standstill (stagnation) cooling unit, e.g. cooling the receiver, with back-up power, and by selecting an adequate PS and relief valves
By raising the plant-room temperature
By completely shutting down the system and power supply

197

Nehéz

What does standstill (stagnation) of a CO₂ system mean, and why is it important?


A state with no compressor operation or refrigerant flow – pressure rises with ambient temperature and may exceed PS
A drop in system temperature
Normal system operation
Improved efficiency

198

Könnyű

Why do CO₂ systems require more advanced automation than traditional systems?


Because there are no valves
They do not require automation
Due to low pressures
Due to the need for precise control of pressure and temperature

199

Nehéz

What must the label of a flammable refrigerant cylinder include?


Only the refrigerant name
Information about the cylinder owner
Only the net weight
The refrigerant name, the UN number, the hazard label (e.g. 2.1 – flammable gas) and basic safety information

200

Nehéz

Why is the absence of a 'flammable refrigerant' label on equipment a serious hazard?


It may lead to the wrong oil being selected
It has no significant effect on safety
It reduces system efficiency
It may lead to the use of tools that are ignition sources

201

Nehéz

Which set of information on the label of a flammable refrigerant cylinder is crucial from a safety perspective?


Manufacturer’s name and country of origin
Name of the substance, hazard label (ADR) / GHS pictogram (CLP), UN number
Cylinder colour and date of manufacture
Gross weight and batch number

202

Közepes

Before charging the unit with refrigerant, it is essential to…


…fill in the unit's data sheet
…carry out a tightness test (and evacuate the system)
…check the compressor suction and discharge connections
…carry out a trial start-up

203

Könnyű

What is the requirement regarding the labelling of an installation containing a flammable substance?


Colour-coding of pipes is sufficient
Labelling is required only in technical rooms
The labelling must indicate the type of substance and the flammability hazard
Labelling is not required for hermetically sealed systems

204

Könnyű

What are the potential consequences of using unsuitable connections in a system containing a flammable substance?


Merely installation difficulties
No impact on safety
Risk of leakage and the formation of an explosive mixture
Merely a reduction in efficiency

205

Nehéz

What is the purpose of gas detectors in a room with a refrigeration system?


Controlling compressor capacity
Measuring refrigerant temperature
Early leak detection and triggering of measures preventing health risks and explosive atmospheres (alarm, ventilation, shut-off)
Monitoring pipe pressure

206

Nehéz

How often should gas detection sensors in a machinery room be checked?


Only after a leak has occurred
Before every start-up of the unit
Once every 5 years
According to the manufacturer's instructions and regulations – at least every 12 months

207

Nehéz

Where should a gas detector be located according to EN 378?


Near the control panel
Where the refrigerant would accumulate: low (near the floor) for refrigerants heavier than air, high (near the ceiling) for lighter ones such as NH₃
Anywhere in the room
Only at the room entrance

208

Könnyű

How should an employee respond when a gas alarm is triggered?


Reduce the pressure in the system
Switch off the system and wait for the alarm to stop
Leave the room immediately and notify their supervisor
Carry on working until they see a leak

209

Nehéz

What safety checks should be carried out when installing a new refrigeration system with a flammable refrigerant?


Only the compressor power
The presence of health and safety signage, adequate ventilation and gas detectors
Only that the air filter is new
The colour of pipes and hoses

210

Könnyű

Gas detectors should be installed in rooms where:


The amount of refrigerant exceeds a specified permissible threshold
The room is less than 5 m²
Ventilation is natural
Any refrigerant is present, regardless of the quantity

211

Nehéz

What are the requirements for emergency exits from a refrigeration machinery room?


At least two exits are required and signage is optional
Outward-opening doors and signed escape routes (number of exits per the standard)
One exit with a sign stating the refrigerant type is sufficient
In small machinery rooms emergency exits need not be signed

212

Nehéz

Which installation measure for a flammable-refrigerant system improves its energy efficiency?


Restricting room ventilation
Omitting the filter-drier
Charging above the nameplate quantity
A thorough tightness test and evacuation (dehydration) of the system

213

Közepes

What information must appear on the label of equipment containing F-gases?


The weight and capacity of the pipework and the colour code of the casing paint
The manufacturer's logo, the unit weight and year of manufacture from the rating plate
That it contains an F-gas, its designation, quantity in kg and t CO₂ eq, and GWP
Only the trade name of the refrigerant and the unit's serial number

214

Könnyű

How do leaks affect systems using flammable refrigerants?


They cause refrigerant loss, reduced efficiency and a fire hazard
They lower the temperature
They improve efficiency
Have no effect

215

Nehéz

Why is it important to limit the refrigerant charge in HC systems?


It doesn't matter
It limits the possibility of reaching a flammable concentration (≥ LFL) in a leak, increasing safety
It increases capacity
It lowers the temperature

216

Könnyű

Why is the cleanliness of heat exchangers in HC systems important?


It doesn’t matter
It increases the pressure
Causes leaks
It improves heat transfer and reduces energy consumption

217

Könnyű

What maintenance measures improve the efficiency of a system using a flammable refrigerant?


Increasing the refrigerant charge
Disabling safety devices
Lack of servicing
Regular checks for leaks and operating parameters

218

Könnyű

How does the correct selection of components affect a system using a flammable refrigerant?


It increases the amount of refrigerant
It lowers the temperature
It doesn’t matter
It ensures safe and optimal operation and minimises energy losses

219

Könnyű

Why is it important to use the correct service tools in HC systems?


It doesn’t matter
It ensures operational safety and reduces refrigerant losses
Causes leaks
It increases energy consumption

220

Könnyű

How does pipe insulation affect the efficiency of systems containing HC?


Causes leaks
It doesn’t matter
It reduces energy losses and improves efficiency
It increases the pressure

221

Nehéz

Which safety class applies to R744?


A1
B2L
A2.
A3

222

Nehéz

In a simple single-stage R744 system without an intermediate receiver (refrigerant flows from the gas cooler directly to the expansion valve), operating transcritically at 90 bar with a gas-cooler outlet temperature of 35 °C, the refrigerant upstream of the expansion valve is…


…a subcooled liquid
…a supercritical fluid
…a two-phase mixture at intermediate pressure
…saturated vapour at intermediate pressure

223

Nehéz

In R744 transcritical systems, the gas cooler outlet valve controls:


The inlet temperature to the gas cooler
The gas cooler fans
The pressure in the gas cooler
The outlet temperature of the gas cooler

224

Könnyű

What is the base unit of temperature according to the International System of Units (Système International d’Unités)?


°F
°R
K
°C

225

Közepes

Which set of information best reflects the content of the equipment records required by Regulation (EU) 2024/573?


Only the date of installation and the installer's name
The make and model of the unit
Operator details, equipment details, type and quantity of refrigerant, and information on servicing and repairs
The owner, installer and service technician of the unit

226

Nehéz

Which statement best describes the behaviour of R717 and mineral compressor oil?


An oil return line cannot be used in R717 systems because the oil is too hot
R717 mixes very well with the oil, which easily returns to the compressor
R717 does not mix with the oil; the oil, being heavier than liquid NH₃, collects beneath it at the lowest points (mainly on the low-pressure side)
R717 does not mix with the oil; the oil collects on the high-pressure side above the R717

227

Nehéz

What is the main reason for using K65 copper tubing in some R744 systems?


They have good low-temperature performance
They come in a wider range of diameters
They bend easily
They can withstand higher pressures

228

Nehéz

Which statement about installing Schrader valves is correct?


When brazing the valve body, the core must be removed, then refitted and tightened to the correct torque
All Schrader cores are suitable for all refrigerants
Schrader valves must not be used in R744 systems
Hydrocarbons leak through Schrader valves

229

Nehéz

Which refrigerant can be detected with phenolphthalein paper?


R744
R717
R1234ze(E)
R1270

230

Nehéz

How does an undercharge affect the high-pressure side (without discharge pressure control)?


Discharge pressure lower, subcooling higher
Discharge pressure higher, subcooling lower
Discharge pressure higher, subcooling higher
Discharge (condensing) pressure and subcooling will both be lower

231

Nehéz

What is the benefit of adding helium as a tracer gas to nitrogen in a pressure test?


Its small atoms pass easily through leaks and are detected
It has a distinctive odour that helps locate the leak
It has a higher pressure than pure nitrogen in the same cylinder
It reacts with refrigerant residues, producing a visible colour change

232

Nehéz

Why should an evacuated R744 system initially be charged with refrigerant in the vapour phase?


To prevent the drain valve on the receiver from opening
To avoid damaging the compressor with liquid CO₂
To charge R744 more slowly and measure it more accurately
To prevent dry ice forming (until approx. 5.2 bar abs is exceeded)

233

Nehéz

If moisture remains in an R744 system because it was not properly evacuated (dehydrated), what is the likely consequence?


Formation of carbonic acid, which damages the system
Excessive discharge pressure
Reduced cooling capacity
Formation of hydrogen fluoride and hydrofluoric acid

234

Nehéz

Which system may require manual oil recovery?


An R717 system
Secondary system using R744
R744 cascade system
Supercritical ‘booster’ system using R744

235

Nehéz

The pressure of R744 at a saturation temperature of 20 °C is approx.


56 bar g
25 bar g
14 bar g
90 bar g

236

Közepes

Who is responsible for keeping the equipment records?


The operator of the unit or system.
The person responsible for risk assessment.
There is no such obligation.
The equipment maintenance technician.

237

Nehéz

Which refrigerant is lighter than air?


R1234ze(E)
R1270
R744
R717

238

Nehéz

What hazards are associated with a safety group A3 refrigerant?


Higher toxicity, no flame propagation
Higher flammability, lower toxicity
Lower flammability, lower toxicity
Lower toxicity, no flame propagation

239

Nehéz

What is the GWP of R32 (per AR4, as used in Regulation (EU) 2024/573)?


0
6
675
3922

240

Nehéz

What factors are taken into account when determining the maximum charge for comfort air-conditioning/heating applications?


Lower flammability limit, height of the indoor unit, floor area
Practical limit, room volume
Practical limit, height of the indoor unit, floor area
Lower flammability limit, room volume

241

Nehéz

What compressor displacement is required for R1270 compared with an R404A compressor in the medium-temperature range (cold room)?


About half
About 1.5 times larger
Similar
About 6 times larger

242

Nehéz

At an ambient temperature of 25 °C, the standstill pressure in the low-pressure stage of an R744 cascade (without standstill cooling) will typically be…


…the same as the relief valve set pressure
…approx. 27.5 bar g
…higher than the maximum allowable pressure (PS) of the low-pressure stage
…the same as the high-pressure switch setting

243

Nehéz

What is the correct definition of critical temperature?


The temperature at which a substance changes from a gaseous to a solid state
The temperature above which there are no distinct liquid and gaseous phases
The temperature at which the vapour pressure of a liquid is equal to the ambient pressure surrounding the liquid
The temperature at which, for certain substances, electrical resistance is zero

244

Nehéz

In the gas cooler of a transcritical system, the supercritical working fluid…


…rejects heat as its temperature falls
…rejects heat as its pressure falls
…rejects heat at constant temperature and pressure
…rejects heat during a phase change

245

Nehéz

R717 is highly corrosive to:


copper (and its alloys)
stainless steel
aluminium
titanium

246

Nehéz

What can be the effect of a relief valve lifting repeatedly?


The valve may not reseat tightly and its set (opening) pressure may decrease
The set pressure increases
The valve stays fully open permanently
The valve no longer opens

247

Közepes

Where are oil traps installed on the suction line?


At the bottom of vertical suction risers with upward flow
Before the safety valve on the suction side
At the inlet to every component of the refrigeration system
Immediately before the compressor suction connection

248

Nehéz

What is the relationship between the pressure (p) and temperature (T) of nitrogen at the start (1) and end (2) of a tightness test (p absolute, T in kelvin)?


p₂ = T₁/(p₁ × T₂)
p₂ = T₂/(p₁ × T₁)
p₂ = (p₁ × T₂)/T₁
p₂ = (p₁ × T₁)/T₂

249

Nehéz

What is the recommended pre-alarm level for fixed leak detection systems for R717?


500,000 ppm
5,000 ppm
50,000 ppm
500 ppm

250

Nehéz

Why are compressors with a separate motor (open type) mostly used in R717 systems?


Because NH₃ attacks copper motor windings, so hermetic compressors with conventional windings are not used
To lower the condensing pressure
To increase the refrigerant charge
Because they are cheaper

251

Nehéz

Which type of compressor is most commonly used in large ammonia systems?


A reciprocating or screw compressor
Diaphragm compressor
Hermetic scroll
Rotary vane compressor

252

Nehéz

How is the capacity of a piston compressor regulated in NH₃ systems?


By reducing the refrigerant charge
By unloading the cylinders or changing the rotational speed
By increasing the condensing pressure
Solely by adjusting the oil volume

253

Nehéz

How is the capacity of a screw compressor most commonly controlled?


By adjusting the oil level
By changing the type of oil
By closing the suction valve
By using a slide valve

254

Nehéz

When is two-stage compression used in NH₃ systems?


Only with water-cooled condensers
At small temperature differences
Only in small systems
At low evaporating temperatures (pressures) and high pressure ratios

255

Nehéz

What is the advantage of two-stage compression over single-stage compression?


Higher efficiency and lower discharge temperature
Lower efficiency
No need for a separator
Higher energy consumption

256

Nehéz

How does an evaporative condenser used in NH₃ systems work?


It utilises the evaporation of water to increase cooling efficiency
It transfers heat only to the air
It does not require a water supply
Operates without a fan

257

Nehéz

What is the function of the liquid separator in an NH₃ system?


Regulates the condensing pressure
It prevents liquid from entering the compressor
It separates oil from the refrigerant
Increases the discharge temperature

258

Közepes

Which symptoms with the compressor running indicate a refrigerant leak (undercharge)?


Low suction pressure, high superheat and negligible subcooling
Sight glass full of liquid and rising oil level in the crankcase
Rising condensing and suction pressures with no superheat
Rising liquid level in the receiver and increasing subcooling

259

Nehéz

What is the purpose of monitoring the liquid level in the separator?


To maintain the correct refrigerant level and prevent the compressor from flooding
To control the condenser fan
To reduce the condensing temperature
To increase the oil volume

260

Nehéz

What is the role of the float switch in NH₃ systems?


It is used to detect leaks
It monitors the liquid level in the tank or separator
It regulates the condensation temperature
It controls the fan’s operation

261

Nehéz

What is a thermosyphon in NH₃ systems?


A system with gravity-driven (natural) circulation of liquid refrigerant caused by density differences, used e.g. for screw compressor oil cooling
A defrosting device
An oil circulation pump
A type of safety valve

262

Nehéz

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


Because the oil mixes only with water
Because NH₃ does not mix with most compressor oils
To increase the amount of refrigerant
To reduce the pressure

263

Nehéz

What is the main function of an oil separator in NH₃ systems?


To increase fan efficiency
To separate the oil from the refrigerant and return the oil to the compressor
To lower the condensation temperature
Removing moisture from the system

264

Nehéz

In which NH₃ system does the refrigerant evaporate completely with superheat in the evaporator, fed by an expansion valve?


An indirect system
A direct-expansion (DX) system
A glycol system
A pumped liquid-recirculation system

265

Nehéz

What is the characteristic feature of a flooded evaporator system?


The evaporator contains a large amount of liquid, which improves heat transfer
The evaporator is filled exclusively with vapour
No separator is used
No level control is required

266

Nehéz

What is the main difference between a direct and an indirect system?


In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load
In an indirect system, no compressor is used
In an indirect system, NH₃ flows directly into the space being cooled
In a direct system, there is no evaporator

267

Közepes

Which components of a refrigeration system are potential leak points subject to leak checks?


Only suction-side components
Joints, valves (including stems), seals (including those on replaceable filters and driers), parts subject to vibration and connections to safety and measuring devices
Only high-pressure-side components
Hermetic compressors, liquid receivers and liquid separators

268

Közepes

What pressure is used for the pressure tightness test of an installation?


The pressure specified in EN 378-2 or by the manufacturer, not exceeding the maximum allowable pressure of the system (PS)
A pressure chosen by the technician based on experience
Always 30 bar
A pressure equal to the maximum pressure measured during operation

269

Közepes

At which points of the unit must the leak check be carried out?


Only on discharge-side components
Only on compressor shut-off valves, solenoid valves and filters
At all points where there is a potential risk of refrigerant leakage
Only at connections of measuring instruments

270

Közepes

When can a unit be considered tight after a pressure test?


When gas bubbles appear after immersion in water
When it has been checked with a fixed electronic detector
When the pressure remains constant during the test (allowing for temperature-related changes); any unexplained pressure drop requires the leak to be located
When the pressure drop does not exceed 0.1 bar regardless of the test duration

271

Közepes

Which legal act currently sets out the obligation to check stationary refrigeration equipment containing F-gases for leaks, and how often this must be done?


Commission Regulation (EC) No 1516/2007
Regulation (EU) 2024/573
Regulation (EU) No 517/2014
Implementing Regulation (EU) 2024/2215

272

Nehéz

Which parts of a refrigeration system should be given particular attention during a leak check?


Compressor and receiver connections, because the pressure is highest there
Joints, valves incl. stems, seals, parts subject to vibration, connections to safety devices
Only compressor connections, because they are the only parts subject to vibration
Only condenser connections, because the refrigerant is liquid there

273

Könnyű

What is the superheat of refrigerant vapour?


The difference between the actual vapour temperature and the saturation temperature corresponding to its pressure (expressed in K)
The amount of heat required to evaporate a liquid
The difference between the saturation temperature and the actual liquid temperature in the liquid line
The difference between the condensing temperature and the ambient temperature

274

Nehéz

Leak checks can be carried out using various methods. Which pair is correct?


Direct and indirect methods
Physical and chemical methods
Material quality control methods and electronic methods
Methods with and without quality control of supplies

275

Nehéz

To whom can leak checks of stationary refrigeration equipment containing F-gases be entrusted?


A person who has carried out such checks before
A natural person holding a certificate covering leak checks (A1, A2 within its charge limit, or E)
An employee appointed by the owner of the installation
Any leak-testing specialist

276

Nehéz

What conditions must be met to use UV dye for leak checking?


It is sufficient that introducing dye into the circuit is technically feasible
It is sufficient to have a UV lamp, dye and safety goggles
A UDT authorisation for pressure testing is required
Manufacturer approval of the method and a certificate covering breaking into the circuit

277

Nehéz

Which leak-checking methods are considered direct methods?


Nitrogen with tracer gas and pressure measurement
1. gas detection devices (portable or fixed leak detection system), 2. UV detection fluid or dye, 3. bubble/foam solutions
Pressure-change measurement and immersion in water
Vacuum test and foam solution

278

Nehéz

What do indirect leak-checking methods involve?


Ultrasonic measurement
Leak detection with UV dye
A visual and manual check and analysis of parameters: pressure, temperature, compressor current, liquid levels and recharge volume
Leak detection with an electronic detector

279

Közepes

How should the pressure be increased during a pressure tightness test?


As quickly as possible
Gradually, in stages, checking for leaks at each level until the test pressure is reached
In one step, by fully opening the nitrogen cylinder valve
In any way

280

Közepes

What electronic equipment should be used for leak checking?


Only hot-cathode devices
Detectors suited to the refrigerant in the system, with appropriate sensitivity, checked periodically
Only detectors with an infrared sensor
Only devices with an 'ion pump' sensor

281

Közepes

What documentation should be checked before starting a leak check?


The equipment records – especially recurring problems and previous leaks
The operator's fixed-asset inventory ledger
Attendance sheets of the plant-room staff for the year
Only the installation invoice and the first start-up report

282

Közepes

What information must be recorded in the leak check report?


Date, number and location of leaks, how they were repaired, technician details and signature
The method used, the time spent on site and the cost of repair
The date, a general note about the leak and the operator's signature
Only the number of leaks found and the date of the check

283

Közepes

What pressure should be used for the pressure tightness test?


Any pressure, at the technician's discretion
A pressure not exceeding the maximum allowable pressure of the system (PS)
Always 2–3 bar
Always 10–12 bar

284

Közepes

What is the temperature glide of a refrigerant?


In zeotropic mixtures, the difference between the temperatures at the start and end of a phase change (boiling or condensation) at constant pressure
The temperature drop of the refrigerant across the expansion valve
A property of single-component refrigerants, for which one saturation temperature corresponds to a given pressure
The temperature rise of the vapour in the compressor

285

Nehéz

What does a vacuum (decay) test involve?


With the pump running, you watch the vacuum gauge reading
The pump runs continuously to hold the required vacuum for the test
After isolating the pump, you check whether the system pressure rises
The pump is restarted every time the system pressure rises

286

Nehéz

How often should leak tests be carried out on equipment containing 1.5 kg of R404A refrigerant (5.9 tonnes of CO₂ equivalent)?


Once every six months.
On initial commissioning.
Only when servicing the unit.
At least once every 12 months.

287

Nehéz

How often should leak tests be carried out on equipment containing 7 kg of R404A refrigerant (27.45 tonnes of CO₂ equivalent)?


At least once every 12 months.
Only when servicing the unit.
Once every six months.
On initial commissioning.

288

Közepes

In which equipment is a leakage detection system required?


Equipment with 5 t CO₂ eq or more of F-gases, regardless of equipment type
Equipment with 30 kg or more of F-gases, regardless of their GWP
Equipment with 50 t CO₂ eq or more of F-gases, regardless of equipment type
Equipment with ≥ 500 t CO₂ eq of Annex I F-gases (or ≥ 100 kg of Annex II Section 1 gases)

289

Nehéz

Under Regulation (EU) 2024/573, a leakage detection system is mandatory when:


the charge is 100 kg or more of ozone-depleting substances
the F-gas charge of the refrigeration equipment is 500 t CO₂ eq or more
the equipment contains a flammable refrigerant in any quantity
the equipment operates in an enclosed space

290

Nehéz

Which leak-checking method may NOT be used by a holder of a Category E certificate?


Visual inspection
Checking with a foaming solution
Leak checking with a fluorescent dye introduced into the circuit
Measurement with a handheld electronic detector

291

Közepes

What should you check before using a portable electronic leak detector?


That it holds a valid UDT inspection certificate
That it suits the refrigerant and has been checked as the manufacturer requires
That it has an infrared sensor, as only this type is permitted
That it has been zeroed close to the suspected leak point

292

Közepes

Which certificate types (A1, A2, B, C, D, E) authorise leak checks of equipment containing F-gases?


Only E
Only A1 and A2
All except D
A1, A2 and E

293

Nehéz

Within what timeframe must a leak test be carried out on a stationary refrigeration system after a leak has been repaired, in accordance with EU Regulation 2024/573 on F-gases?


At any time.
Between 24 hours and 1 month after the repair.
Immediately after the repair.
At the next periodic inspection.

294

Nehéz

How often must refrigeration equipment containing ≥500 t CO₂ eq of F-gases be checked if (contrary to Article 6) no leakage detection system is installed?


Every month
Every 3 months
Every 6 months
Every 12 months

295

Közepes

Why is it advisable to subcool the liquid refrigerant?


To ensure that liquid free of vapour bubbles enters the expansion valve
To allow a smaller expansion valve to be used
To lower the evaporating temperature in the evaporator
To allow a condenser with a smaller heat-exchange surface to be used

296

Közepes

What must be done after repairing a leak in the refrigeration unit of a refrigerated trailer?


Charge an alternative refrigerant, start up and measure the parameters
Issue the invoice and leave the leak check to the next periodic service
Visually inspect only the bolted and brazed joints near the repair
Update the equipment records and carry out a leak check (it may be done directly after repair)

297

Közepes

Recovery of fluorinated greenhouse gases means:


The reprocessing of fluorinated greenhouse gases to achieve their specified standard properties.
The final decommissioning and withdrawal from service or use of a product or piece of equipment containing fluorinated greenhouse gases.
The reuse of fluorinated greenhouse gases following a basic purification process.
The collection and storage of fluorinated greenhouse gases from containers, products and equipment during maintenance or servicing or prior to their disposal.

298

Közepes

Who is authorised to recover refrigerant from stationary refrigeration equipment containing F-gases?


The administrator of the operator's account in the register
The operator
A natural person holding a certificate of the relevant type (A1; A2. or D within their charge limit)
The owner of the installation

299

Közepes

How must recovered refrigerants be stored?


In a labelled recovery cylinder with a dual valve and a valid inspection
In any used refrigerant cylinder, provided it is leak-tight
In any pressure vessel that has some form of approval
In a disposable (non-refillable) cylinder that held the same refrigerant

300

Közepes

When should the recovery of fluorinated greenhouse gases be carried out:


Before each leak test of the equipment.
Before the final disposal of equipment and, where applicable, during its servicing and maintenance.
Always during servicing and maintenance of equipment.
Only prior to the final disposal of equipment.

301

Közepes

What should be done if recovered refrigerant is contaminated (e.g. with acid, air or moisture)?


Clean the mixture yourself using a filter-drier
Hand it over to a specialised, authorised company for reclamation or destruction
Add a special contaminant neutraliser
Pass it through a particle filter and reuse it

302

Közepes

What should be done if different refrigerants have been mixed in a storage cylinder?


Separate the mixture into its components yourself
Pass it through a filter-drier and reuse it
Hand the mixture over to an authorised company – as a rule for destruction
Add a special refrigerant to the mixture

303

Közepes

How does push-pull refrigerant recovery work?


Refrigerant is drawn alternately from the suction and discharge sides of the compressor
The recovery unit draws vapour from the system and condenses it in the cylinder
The recovery unit draws vapour from the recovery cylinder and pushes it into the system; the pressure difference forces liquid refrigerant out of the system into the cylinder
Nitrogen is injected into the system, pushing the refrigerant into the atmosphere

304

Közepes

What are the options for managing waste refrigerant?


Recycling, reclamation, destruction
Disposal, storage
Reclamation, recovery
Recovery, disposal

305

Közepes

Which management option restores recovered refrigerant to a quality equivalent to virgin product, so that it can be used by any undertaking?


Recycling
Storage
Reclamation
Destruction

306

Közepes

The lower the evaporating temperature, …


…the lower the density of the suction vapour and the lower the refrigerant mass flow rate
…the lower the density of the suction vapour and the greater the cooling capacity of the compressor
…the greater the density of the suction vapour and the lower the refrigerant mass flow rate
…the greater the density of the suction vapour and the greater the refrigerant mass flow rate

307

Közepes

How must transportable pressure vessels (e.g. refrigerant cylinders) be marked?


The marking is optional
With the manufacturer's logo and date of manufacture
Among other things: the number of the design and testing standard, marks of the approving country and the inspection body, the date of the initial inspection, and the manufacturer's and operational marks
Only with weight and capacity marks

308

Közepes

The recovery of refrigerants does not require the use of:


Hoses with shut-off valves.
An electronic leak detector.
Scales with a measurement range suitable for the size of the cylinder being filled.
A refrigerant recovery station.

309

Közepes

What functions does the compressor perform in a refrigeration system?


The compressor draws in refrigerant vapour from the evaporator, compresses it, and then forces it into the condenser, raising the pressure to the required condensing pressure.
The compressor creates a vacuum on the suction side of the system
The compressor compresses ambient air and increases the pressure of the refrigerant.
The compressor condenses the refrigerant.

310

Könnyű

What is the compression ratio of a compressor?


The amount of refrigerant compressed per cycle relative to heat capacity
The ratio of absolute discharge pressure to absolute suction pressure (pc/po)
The ratio of discharge pressure to the effective capacity of the compressor (p/Vk)
The ratio of suction pressure to discharge pressure (po/pc)

311

Közepes

What is compressor flooding (liquid slugging)?


A large amount of liquid refrigerant in a flooded evaporator, which is a normal operating condition
Excess oil in the condenser
Flooding of the compressor by rainwater
Liquid refrigerant or oil entering the compression chamber

312

Közepes

Within what range is the compressor motor speed typically controlled using a frequency inverter?


By a maximum of 10%
From approximately 10% to 90% of nominal capacity
Speed control does not change the cooling capacity
Approximately 30 to 75 Hz, corresponding to about 60–150% of nominal capacity (depending on the compressor manufacturer)

313

Könnyű

What is the theoretical displacement (swept volume flow) of a compressor?


The volume of a single cylinder in cm³
The volume of vapour drawn in per unit of time, determined by the compressor's geometry and speed (stated by the manufacturer, e.g. in m³/h)
The volume of refrigerant flowing in one piston cycle under actual operating conditions
A value expressed by the coefficient of performance (COP)

314

Közepes

Why is it essential to observe the correct phase sequence for scroll compressors and screw compressors?


Because the motor speed would decrease, and consequently the compressor’s capacity.
Because changing the phase sequence would reverse the direction of rotation of the compressor rotors, which could result in damage to the compressors.
Because these types of compressors are sensitive to voltage drops.
Because this type of compressor has difficulty starting up if the phase sequence is changed.

315

Közepes

What compression ratio should each stage of a two-stage vapour-compression system have (rule of thumb)?


Less than approximately 8
Greater than 18
Greater than 10
Equal to 1

316

Közepes

Why is a shaft seal necessary in open-type compressors?


Only to prevent oil leakage
To prevent air from entering and refrigerant from leaking out of the compressor
To protect the crankshaft bearing
To ensure the bearing remains lubricated

317

Közepes

How can you check whether the liquid refrigerant is sufficiently subcooled?


Check by touch whether the condenser outlet is noticeably colder than ambient
Compare the liquid-line temperature with the saturation temperature at the measured condensing pressure
Check whether the whole evaporator surface is covered with an even layer of frost
Check whether the liquid distributor upstream of the evaporator feels warm

318

Közepes

Why is the compressor crankcase heated?


To keep the lubricating oil liquid
To dehydrate the oil
To increase dissolution of refrigerant in the oil and improve its viscosity
To limit refrigerant migration into, and dissolution in, the oil during standstill

319

Könnyű

What is the clearance (dead) volume of a reciprocating compressor?


The space between the underside of the piston and the crankcase cover
The volume between the valve plate and the piston at bottom dead centre
The volume between the valve plate and the piston crown at top dead centre
The space between the side of the piston and the cylinder

320

Közepes

What are compressor packs (racks)?


Sets of compressors connected in any configuration
Units with two-stage compressors
Several air-cooled condensers
Several compressors connected in parallel on a common frame with common suction and discharge headers

321

Közepes

What is the main advantage of multi-compressor packs?


Stepwise capacity matching to demand, plus redundancy
A smaller refrigerant charge than a single-compressor system
No need for compressor controls and safety devices
Low purchase cost and easy installation without special controls

322

Közepes

What is meant by the operating envelope (application range) of a compressor?


A range determined by the evaporating temperature at a given ambient temperature
The capacity, refrigerant type and dimensions of the compressor
The permissible range of evaporating and condensing temperatures (to, tk), or the corresponding pressures, within which the compressor may operate
A range determined only by the evaporating temperature

323

Közepes

What are the basic functions of oil in a compressor?


Increasing the cooling capacity of the refrigerant
Lubricating bearings and sliding surfaces, removing heat, and sealing clearances (e.g. between piston and cylinder, or rotors)
Absorbing moisture from the refrigerant
Sealing leaks that develop in the installation

324

Közepes

What are the most effective ways of controlling compressor cooling capacity?


Pressure control valves
Changing the displacement: varying the rotational speed or unloading cylinders
Partially covering the evaporator
An expansion valve

325

Közepes

What does hot-gas bypass capacity control involve?


Part of the hot discharge gas is passed through a bypass valve to the suction side (or evaporator inlet), reducing the effective capacity
High-pressure liquid is injected into the suction to increase capacity
The compressor speed is varied
Bypass is not used for capacity control

326

Közepes

What is the fundamental difference between hermetic and semi-hermetic compressors?


The semi-hermetic compressor has no motor inside the casing
The semi-hermetic casing is bolted (can be opened); the hermetic one is welded
Both can be dismantled; they differ only in cooling capacity
Semi-hermetic compressors run more quietly as a complete unit

327

Közepes

How does a scroll compressor work?


It is a type of piston-type device.
It is a positive-displacement compressor in which compression results from the interaction of a fixed and an orbiting scroll.
It uses two screws to compress the refrigerant.
A scroll compressor is also known as a turbo compressor.

328

Közepes

What physical process takes place in the evaporator?


The refrigerant condenses
The liquid refrigerant evaporates, absorbing heat, and the vapour is slightly superheated at the outlet
The refrigerant is subcooled as a liquid
The secondary fluid (glycol, water) evaporates while the refrigerant condenses

329

Közepes

What is the purpose of compressor capacity control?


To ensure compressor lubrication
To match the cooling capacity to the current demand
To match capacity to the condensing temperature
To increase the condensing pressure

330

Közepes

Why is inverter speed control advantageous for refrigeration compressors?


It enables continuous, smooth control of cooling capacity
It increases compressor capacity above nominal at any frequency
Reducing the speed improves oil return to the compressor
It can be used with any compressor to ensure lubrication

331

Közepes

Does the suction gas temperature affect the cooling capacity of the compressor?


No – capacity depends only on the compressor displacement
Yes – higher temperature lowers vapour density, mass flow and capacity
Yes, but only if the suction gas is deeply cooled
Yes, but only in reciprocating compressors, not scroll

332

Közepes

In the case of compressor units fitted with an oil level control system, is it necessary to install the compressors at the same height?


No.
Only screw compressors.
Yes.
Only scroll compressors.

333

Közepes

What functions does a compressor powered by the vehicle’s engine perform in a transport refrigeration system?


This compressor draws in refrigerant vapour from the evaporator, compresses it and then forces it into the condenser whilst the vehicle’s engine is running.
The compressor compresses ambient air and increases the pressure of the refrigerant.
This compressor creates a vacuum on the suction side of the system whilst the vehicle’s engine is switched off.
This compressor condenses the refrigerant whilst the vehicle is in motion.

334

Közepes

Which media most commonly absorb heat from the refrigerant in the condenser?


Only a water–glycol mixture
Air or water
Air and CO₂
Ammonia

335

Közepes

What is the function of the condenser in refrigeration systems?


Releasing only the heat absorbed in the evaporator into the surroundings
Absorption of heat rejected in the regenerative heat exchanger
Releasing only the heat from the compressor into the surroundings
Releasing to the environment the heat absorbed in the evaporator and the heat added during compression

336

Közepes

If the refrigerant temperature on the high-pressure side is above its critical temperature, condensation…


…does not depend on temperature
…occurs provided a special condenser is used
…always occurs regardless of temperature
…does not occur

337

Közepes

How is liquid subcooling usually achieved in a refrigeration system?


By dissolving the refrigerant in oil
With an additional heat exchanger using liquid nitrogen
With hot high-pressure vapour
In the final section of the condenser (or in an additional subcooler)

338

Közepes

What is the purpose of condenser fan speed control?


To keep the condensing pressure at the correct level
To reduce energy efficiency
To disperse refrigerant in the event of a leak
Only to protect against exceeding the maximum condensing pressure

339

Közepes

Which international agreement introduced the global phase-down of HFC production and consumption?


The Vienna Convention for the Protection of the Ozone Layer
The Paris Agreement
The Kyoto Protocol
The Kigali Amendment to the Montreal Protocol

340

Közepes

Which international treaty governs the phase-out of ozone-depleting substances (CFCs, HCFCs)?


The Montreal Protocol
The Stockholm Convention
The Paris Agreement
The UN Framework Convention on Climate Change (UNFCCC)

341

Nehéz

What is the basis of the GWP values in Regulation (EU) 2024/573?


AR4 for all substances
Each Member State sets its own GWP values
For HFCs (Annex I) – mainly the IPCC Fourth Assessment Report (AR4); for HFOs and non-fluorinated substances (Annexes II and VI) – the Sixth Assessment Report (AR6)
AR6 for all substances

342

Nehéz

An air conditioner (not hermetically sealed) contains 2.5 kg of R410A (GWP 2088). How often must it be checked for leaks?


Every 3 months
No checks required (below 3 kg)
At least every 12 months (5.22 t CO₂ eq)
Every 6 months

343

Nehéz

When is labelled hermetically sealed equipment containing HFCs (Annex I) exempt from leak checks?


Always, regardless of charge
Never – hermetically sealed equipment is always checked
When it contains less than 5 t CO₂ eq
When it contains less than 10 t CO₂ eq, and in residential buildings also when it contains less than 3 kg of F-gases

344

Nehéz

Is a chiller containing 50 kg of R1234ze(E) subject to leak checks under Regulation (EU) 2024/573?


No – HFOs are not subject to leak checks
No – the threshold is 5 t CO₂ eq and 50 kg of R1234ze is below 1 t CO₂ eq
Yes – at least every 6 months (every 12 months with a leakage detection system)
Yes – every 12 months, because its GWP is low

345

Nehéz

In 2026, may an existing refrigeration installation using R404A (GWP 3922) be topped up with virgin refrigerant?


Yes – bans apply only to new equipment
No – only reclaimed or recycled R404A is allowed (until 1 January 2030)
Yes – the ban applies only to equipment ≥40 t CO₂ eq
Yes, if the equipment has a leakage detection system

346

Nehéz

After 1 January 2026, may an R410A (GWP 2088) air conditioner be serviced using virgin R410A?


No – the ban covers all HFCs
No – the ban covers all refrigerants with GWP ≥ 750
Yes – the servicing ban for air conditioners and heat pumps covers F-gases with GWP ≥ 2500
Only with reclaimed refrigerant

347

Közepes

Can HFC refrigerant recovered during a repair be put straight back into the same equipment without any cleaning (filtering/drying)?


No – recovered F-gas may be used for filling only after it has been recycled or reclaimed
Yes, always
Yes, if less than 24 hours have passed
Yes, if the operator agrees

348

Közepes

Who may purchase HFCs for servicing refrigeration equipment?


Only a person holding the relevant certificate or an undertaking employing such persons
Only the equipment operator
Any adult
Any business

349

Közepes

Under what condition may non-hermetically sealed split air conditioning charged with F-gas be sold to an end user?


When evidence is provided that installation will be carried out by a certified undertaking
When the user signs a statement that they will install it themselves
Unconditionally
Only if the unit contains less than 3 kg of refrigerant

350

Közepes

By when must the holder of an F-gas certificate issued under Regulation (EU) No 517/2014 first complete refresher training or an evaluation process?


By 12 March 2025
By 31 December 2030
Never – the certificate is valid indefinitely
By 12 March 2029 (and then at least every 7 years)

351

Közepes

What must the holder of a Category I certificate (Regulation 2015/2067) do to continue using it?


Apply for an extension without training
Nothing – Category I automatically becomes A1
Update their knowledge to the level of Certificate E
Update their knowledge and skills to the level of Certificate A1 (Annex I to Regulation 2024/2215)

352

Közepes

What does Certificate C under Implementing Regulation (EU) 2024/2215 authorise?


All activities in Article 2(1) in relation to ammonia (NH₃)
Leak checks without breaking into the circuit
Recovery of F-gases from equipment <3 kg
All activities in relation to CO₂

353

Közepes

May a person enrolled in a certification training course carry out certified activities?


Yes – under the supervision of a certified person, for no more than 24 months in total
Yes – independently, for 6 months
Yes – with no time limit, if employed by a certified company
No, never

354

Közepes

How long must the operator keep the records of equipment subject to leak checks, if they are not kept in a national database?


At least 5 years
Until the equipment is decommissioned
At least 2 years
At least 1 year

355

Nehéz

Since 1 January 2025, may a new single-split air conditioner containing 1.5 kg of R410A be placed on the market?


Yes – the ban applies from 2029
No – single splits <3 kg with F-gases of GWP ≥ 750 are banned
Yes – the ban applies only to units >12 kW
Yes, if the unit is hermetically sealed

356

Nehéz

From when is it prohibited to place on the market split air-to-air systems up to 12 kW containing F-gases with GWP ≥150 (unless required for safety)?


From 1 January 2029
From 1 January 2035
From 1 January 2025
From 1 January 2027

357

Nehéz

Which persistent atmospheric degradation product of R1234yf is classed as a PFAS?


Carbon dioxide
Ozone
Trifluoroacetic acid (TFA)
Carbonic acid

358

Közepes

What distinguishes class 2L refrigerants from class 2?


No lower flammability limit
Higher toxicity
Heat of combustion above 19 MJ/kg
A maximum burning velocity of no more than 10 cm/s

359

Közepes

What is the lower flammability limit (LFL) of propane R290?


Approx. 1.8 kg/m³
Approx. 0.038 kg/m³ (approx. 2.1% by volume)
Approx. 0.38 kg/m³
Approx. 0.307 kg/m³

360

Nehéz

What is the maximum R290 charge per circuit of a commercial refrigerating appliance (e.g. a cabinet) according to EN IEC 60335-2-89:2022?


1.5 kg
13 × LFL ≈ 494 g
1.2 kg
150 g

361

Nehéz

Calculate the maximum R32 charge (LFL = 0.307 kg/m³) for a wall-mounted air conditioner (h₀ = 1.8 m) in a 20 m² room using m_max = 2.5 × LFL^1.25 × h₀ × A^0.5.


approx. 0.46 kg
approx. 13.8 kg
approx. 4.6 kg
approx. 1.5 kg

362

Közepes

Equipment marked 'Ex II 3G' may be used in zone:


0
1
2 (explosive gas atmosphere unlikely and short-lived)
20 (dusts)

363

Közepes

How is explosion hazard zone 2 defined?


An explosive atmosphere is present continuously or for long periods
An explosive atmosphere is likely to occur in normal operation
An explosive atmosphere is not likely in normal operation and, if it occurs, persists only for a short period
An area where flammable refrigerants are never used

364

Közepes

Under which UN number is propane (R290) carried under ADR?


UN 3252
UN 1005
UN 1978
UN 3337

365

Nehéz

What is the maximum quantity of R290 (class 2, group F) that may be carried per transport unit under the ADR 1.1.3.6 exemption?


333 kg
20 kg
Unlimited
1000 kg

366

Közepes

At what concentration should a portable flammable gas detector used for R290 work raise an alarm at the latest?


At 5% propane by volume
No higher than 25% of LFL
At 100% of LFL
At 150% of LFL

367

Közepes

How should a recovery cylinder be prepared before filling it with a hydrocarbon refrigerant?


No preparation is needed
Evacuate it (no air) and label it for the specific flammable refrigerant
Purge it with compressed air
Partly fill it with nitrogen to 5 bar

368

Közepes

What is the correct approach in a risk analysis before work on an HC system?


Having a fire extinguisher is sufficient
First eliminate hazard sources (e.g. ignition sources); where this is not possible, identify them and apply mitigating measures (ventilation, detection, PPE)
First select PPE, then possibly remove ignition sources
The risk analysis is done after the work is finished

369

Nehéz

What is the charge limit m₃ = 130 m³ × LFL for R290 (LFL = 0.038 kg/m³) according to IEC 60335-2-40?


approx. 4.94 kg
approx. 13 kg
approx. 0.99 kg
approx. 0.15 kg

370

Közepes

Which property of ammonia helps people detect a leak early?


It is denser than air
It is odourless
A very low odour threshold (a few ppm)
It is yellow in air

371

Közepes

What hazard does a large CO₂ leak in an enclosed room pose to people?


CO₂ is completely safe
Explosion of the mixture with air
Accumulation near the floor and asphyxiating/toxic effects at high concentrations
Formation of hydrogen fluoride

372

Nehéz

Why does the efficiency of transcritical CO₂ systems fall in warm climates, and how is this mitigated?


Efficiency does not depend on climate
CO₂ freezes in the gas cooler – heaters are used
Gas cooler pressure drops – extra charge is added
At high ambient temperatures the system operates transcritically with large throttling losses – parallel compression and ejectors are used, among others

373

Közepes

What is floating head pressure and what does it achieve?


It means switching condenser fans off periodically
It keeps a constant high condensing pressure all year
It increases subcooling by flooding the condenser
It lets the condensing pressure fall with ambient temperature, reducing compressor work and raising COP (requires an expansion valve that works at a small pressure difference)

374

Közepes

How do SEER/SCOP differ from EER/COP?


SEER/SCOP apply only to natural-refrigerant equipment
EER/COP are always higher than SEER/SCOP
SEER/SCOP are seasonal indicators accounting for part load and climate (EN 14825); EER/COP refer to a single operating point (EN 14511)
There is no difference – they are synonyms

375

Közepes

Which design approach can significantly reduce the F-gas charge of a large refrigeration installation?


Omitting pipe insulation
Larger liquid-line diameters
Adding a second liquid receiver
An indirect (secondary-coolant) system or a cascade with a natural refrigerant in the low stage, plus heat exchangers with small internal volume

376

Közepes

Why must the charge of small, critically charged R290 systems be weighed to within a few grams during service?


Because scales are not needed – charging is done by sight glass
Small charge deviations significantly change superheat/subcooling and efficiency, and overcharge increases the risk in a leak
Because extra R290 improves efficiency
Because R290 is more expensive than HFCs

377

Közepes

Which information must be entered in the equipment records after a leak check?


Only the equipment's energy consumption
Only the operator's signature
Only the date of the check
The date and result of the check and the identity of the undertaking and person who performed it (with certificate number)

378

Közepes

What must be done when an indirect method (e.g. parameter analysis) indicates a possible leak?


Record it and check at the next periodic inspection
Top up the refrigerant and end the check
Nothing – indirect methods are sufficient
Carry out a direct-method examination to locate the leak