F-Gas English Low GWP

Minden kérdés
HFC | Flammable | CO₂ | NH₃
Könnyű kérdések | Közepes nehézségű kérdések | Nehéz kérdések

1

Közepes

What is R1270?


Propane
Propene (propylene)
Isobutane
n-Butane

2

Közepes

What is the main design difference in hydrocarbon refrigeration systems?


Higher operating pressures
No need for safety measures
Lower energy efficiency
The need to eliminate ignition sources and limit the charge because of the refrigerant's flammability

3

Közepes

How do compressors used in hydrocarbon systems differ?


They must be approved by the manufacturer for the specific flammable refrigerant (e.g. electrical components that are not ignition sources, suitable oil)
There is no difference
They need no lubrication
They must operate at higher pressures than HFC compressors

4

Közepes

What distinguishes class 2L refrigerants from class 2?


No lower flammability limit
A maximum burning velocity of no more than 10 cm/s
Higher toxicity
Heat of combustion above 19 MJ/kg

5

Közepes

What is the lower flammability limit (LFL) of propane R290?


Approx. 1.8 kg/m³
Approx. 0.307 kg/m³
Approx. 0.38 kg/m³
Approx. 0.038 kg/m³ (approx. 2.1% by volume)

6

Közepes

Equipment marked 'Ex II 3G' may be used in zone:


0
20 (dusts)
2 (explosive gas atmosphere unlikely and short-lived)
1

7

Közepes

How is explosion hazard zone 2 defined?


An explosive atmosphere is not likely in normal operation and, if it occurs, persists only for a short period
An area where flammable refrigerants are never used
An explosive atmosphere is present continuously or for long periods
An explosive atmosphere is likely to occur in normal operation

8

Közepes

Under which UN number is propane (R290) carried under ADR?


UN 1005
UN 1978
UN 3252
UN 3337

9

Közepes

At what concentration should a portable flammable gas detector used for R290 work raise an alarm at the latest?


No higher than 25% of LFL
At 100% of LFL
At 5% propane by volume
At 150% of LFL

10

Közepes

How should a recovery cylinder be prepared before filling it with a hydrocarbon refrigerant?


Evacuate it (no air) and label it for the specific flammable refrigerant
No preparation is needed
Purge it with compressed air
Partly fill it with nitrogen to 5 bar

11

Közepes

What is the correct approach in a risk analysis before work on an HC system?


Having a fire extinguisher is sufficient
The risk analysis is done after the work is finished
First select PPE, then possibly remove ignition sources
First eliminate hazard sources (e.g. ignition sources); where this is not possible, identify them and apply mitigating measures (ventilation, detection, PPE)

12

Közepes

Why must the charge of small, critically charged R290 systems be weighed to within a few grams during service?


Small charge deviations significantly change superheat/subcooling and efficiency, and overcharge increases the risk in a leak
Because scales are not needed – charging is done by sight glass
Because extra R290 improves efficiency
Because R290 is more expensive than HFCs