1

Stredne ťažká

Why is ammonia (R717) classed as a toxic refrigerant?


It severely irritates the respiratory tract, eyes and skin, and is poisonous when inhaled at higher concentrations
Because it is colourless and odourless and therefore hard to detect
Because it is heavier than air and displaces oxygen
Because it does not react with water, making neutralisation difficult

2

Ťažká

What is the main difference between a dry-expansion and a flooded evaporator?


In a dry-expansion evaporator the refrigerant completely evaporates and is superheated in the evaporator; in a flooded one part of the refrigerant remains liquid (incomplete evaporation, no superheat)
A dry-expansion evaporator is filled with liquid, a flooded one with vapour
A dry-expansion evaporator needs no expansion valve, a flooded one does
A dry-expansion evaporator always has a lower pressure than a flooded one

3

Ťažká

What is the typical pressure in the evaporator of an R717 deep-freeze system (below −40 °C)?


Atmospheric pressure, approx. 1 bar abs
Below atmospheric (approx. 0.7 bar abs at −40 °C)
Positive pressure of 5–10 bar
Positive pressure of 10–20 bar

4

Ľahká

What is the basic requirement when charging a system with R717 (NH₃)?


Charging can be carried out without personal protective equipment
NH₃ can be charged together with air
Charging should take place in a well-ventilated area using appropriate personal protective equipment
Charging must only take place at temperatures below 0°C

5

Ťažká

How is oil managed in R717 systems?


Oil collecting at the lowest points of vessels is regularly checked and drained, because it impairs heat transfer
Oil can be mixed with any refrigerant
Oil has no effect on system operation
Oil requires no monitoring

6

Ľahká

What is the correct procedure for recovering R717 from a system?


The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃
The refrigerant can be drained into the sewer system
The gas can be released into the atmosphere
Recovery is not required

7

Ľahká

How should R717 (NH₃) be stored?


In any open containers
In unmarked plastic containers
In sealed, labelled containers, in a cool and well-ventilated place
Near heat sources

8

Ťažká

What should be done with contaminated R717?


Purify it or send it for disposal in accordance with regulations
Release it into the atmosphere
Continue to use it without restriction
Dilute it with water and reuse it

9

Ľahká

What is the main hazard associated with an R717 leak during maintenance work?


Toxic to humans and may cause chemical burns
No risk whatsoever
Damage to electrical equipment only
Increased cooling efficiency

10

Ťažká

What should be done if an NH₃ leak is detected?


Evacuate people immediately and raise the alarm; stop the leak only if it is safe to do so and with suitable PPE (respiratory protection)
Increase the pressure in the system
Carry on working with the room door open
Carry on working wearing a dust mask

11

Ťažká

What role do scrubbers play in NH₃ systems?


They increase the pressure in the system
Neutralise ammonia through absorption in a liquid (e.g. water)
They are used to measure temperature
They store the refrigerant

12

Ťažká

How should the system be prepared before filling with R717?


Simply start it up
The pressure must be increased above the standard level
Check for leaks, remove air and moisture, and create a vacuum
There is no need to check it

13

Ťažká

What are the transport requirements for R717?


It can be carried without labelling
It must be carried in suitable, labelled packagings in accordance with ADR (UN 1005, class 2, code 2TC)
It can be carried in open containers
Transport is not regulated

14

Ľahká

What personal protective equipment is required when working with NH₃?


Workwear only
No requirements
Safety goggles, gloves and respiratory protective equipment
Only a safety helmet

15

Ťažká

Which statement best describes the behaviour of R717 and mineral compressor oil?


R717 mixes very well with the oil, which easily returns to the compressor
R717 does not mix with the oil; the oil collects on the high-pressure side above the R717
An oil return line cannot be used in R717 systems because the oil is too hot
R717 does not mix with the oil; the oil, being heavier than liquid NH₃, collects beneath it at the lowest points (mainly on the low-pressure side)

16

Ťažká

Which refrigerant can be detected with phenolphthalein paper?


R1234ze(E)
R744
R717
R1270

17

Ťažká

Which system may require manual oil recovery?


Secondary system using R744
Supercritical ‘booster’ system using R744
R744 cascade system
An R717 system

18

Ťažká

Which refrigerant is lighter than air?


R717
R744
R1270
R1234ze(E)

19

Ťažká

R717 is highly corrosive to:


aluminium
stainless steel
copper (and its alloys)
titanium

20

Ťažká

What is the recommended pre-alarm level for fixed leak detection systems for R717?


500 ppm
5,000 ppm
50,000 ppm
500,000 ppm

21

Ťažká

Why are compressors with a separate motor (open type) mostly used in R717 systems?


To increase the refrigerant charge
To lower the condensing pressure
Because NH₃ attacks copper motor windings, so hermetic compressors with conventional windings are not used
Because they are cheaper

22

Ťažká

Which type of compressor is most commonly used in large ammonia systems?


Hermetic scroll
A reciprocating or screw compressor
Rotary vane compressor
Diaphragm compressor

23

Ťažká

How is the capacity of a piston compressor regulated in NH₃ systems?


Solely by adjusting the oil volume
By reducing the refrigerant charge
By increasing the condensing pressure
By unloading the cylinders or changing the rotational speed

24

Ťažká

How is the capacity of a screw compressor most commonly controlled?


By using a slide valve
By adjusting the oil level
By changing the type of oil
By closing the suction valve

25

Ťažká

When is two-stage compression used in NH₃ systems?


Only with water-cooled condensers
At low evaporating temperatures (pressures) and high pressure ratios
At small temperature differences
Only in small systems

26

Ťažká

What is the advantage of two-stage compression over single-stage compression?


Higher energy consumption
Lower efficiency
No need for a separator
Higher efficiency and lower discharge temperature

27

Ťažká

How does an evaporative condenser used in NH₃ systems work?


It transfers heat only to the air
It does not require a water supply
Operates without a fan
It utilises the evaporation of water to increase cooling efficiency

28

Ťažká

What is the function of the liquid separator in an NH₃ system?


Increases the discharge temperature
It prevents liquid from entering the compressor
It separates oil from the refrigerant
Regulates the condensing pressure

29

Ťažká

What is the purpose of monitoring the liquid level in the separator?


To control the condenser fan
To reduce the condensing temperature
To maintain the correct refrigerant level and prevent the compressor from flooding
To increase the oil volume

30

Ťažká

What is the role of the float switch in NH₃ systems?


It monitors the liquid level in the tank or separator
It regulates the condensation temperature
It is used to detect leaks
It controls the fan’s operation

31

Ťažká

What is a thermosyphon in NH₃ systems?


An oil circulation pump
A system with gravity-driven (natural) circulation of liquid refrigerant caused by density differences, used e.g. for screw compressor oil cooling
A defrosting device
A type of safety valve

32

Ťažká

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


To reduce the pressure
Because NH₃ does not mix with most compressor oils
To increase the amount of refrigerant
Because the oil mixes only with water

33

Ťažká

What is the main function of an oil separator in NH₃ systems?


To lower the condensation temperature
To increase fan efficiency
Removing moisture from the system
To separate the oil from the refrigerant and return the oil to the compressor

34

Ťažká

In which NH₃ system does the refrigerant evaporate completely with superheat in the evaporator, fed by an expansion valve?


A direct-expansion (DX) system
A pumped liquid-recirculation system
A glycol system
An indirect system

35

Ťažká

What is the characteristic feature of a flooded evaporator system?


The evaporator contains a large amount of liquid, which improves heat transfer
No separator is used
No level control is required
The evaporator is filled exclusively with vapour

36

Ťažká

What is the main difference between a direct and an indirect system?


In a direct system, there is no evaporator
In an indirect system, no compressor is used
In an indirect system, NH₃ flows directly into the space being cooled
In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load

37

Stredne ťažká

Which property of ammonia helps people detect a leak early?


It is yellow in air
It is odourless
A very low odour threshold (a few ppm)
It is denser than air